CURRENT TRANSFORMERS
CT with primary winding or
with primary bar or
ring CT
IEC 61869 standards or, on request, others (ANSI, CSA….)
For indoor or for outdoor
Insulation up to 41,5 kV
Primary current up to 50000 A
Secondary current 5 A or 1 A
Short time thermal current up to 100 KA/1s
Accuracy class up to Cl. 0,1

CTs Selection guide 1.25 MB

INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
Mod: ADR17C
Series: CGS
- Highest insulation level 17,5/38/95 kV
- Rated primary current up to 2500 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- Dimensions in accordance with DIN 42600 Schmale Bauform
- Homologation PTB 20.21/97.53
- On request: sealable cover on secondary terminals
- On request: capacitive tap

Mod: ADR17C Serie: DIN 377.13 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ADR17E
Series: CGS
- Highest insulation level 17,5/38/95 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ADR17E Serie: CGS 277.17 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY BAR
MOD: AWR17J
Series: CGS
- Highest insulation level 17,5/38/95 kV
- Rated primary current up to 2500 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR17J Serie: CGS 183.17 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY BAR
MOD: AWR12E
Series: CGS
- Highest insulation level 12/28/75 kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR12E Serie: CGS 153.17 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY BAR
MOD: AWR17H
Series: CGS
Highest insulation level 17,5/38/95 kV
Rated primary current up to 2500 A
Rated secondary current 5 or 1 A
With one or two ratios obtained by secondary taps
Up to three cores
Short time thermal current 100 Ipn/1s (max 60 kA/1s)
Frequency: 50 or 60 Hz
According to IEC 60044-1; other Standards (ANSI, CSA…) on request
Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
Protection class: 5P10 … 5P30
The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
On request: sealable cover on secondary terminals
On request: capacitive tap

MOD: AWR17H Serie: CGS 177.69 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: SKG17/2
Series: BALTEAU
- Highest insulation level 17,5/38/95 kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: SKG17/2 Serie: BALTEAU | Disegno di ingombro 2000A 334.93 KB

MOD: SKG17/2 Serie: BALTEAU | Disegno di ingombro 1500A 369.39 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RKC12
Series: BALTEAU
- Highest insulation level 12/28/75 kV
- Rated primary current up to 100 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 16 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: RKC12 Serie: CGS 175.26 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR24D
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 600 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
- With only one core
- Short time thermal current 100 Ipn/1s (max 30 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ASR24D Serie: CGS 234.63 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR24E
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 600 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 30 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ASR24E Serie: CGS 234.48 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY BAR
MOD: AWR24B
Series: CGS
- Highest insulation level 24/50/125
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24B Serie: CGS 153.17 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AWR24C
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 1250 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24C Serie: CGS 260.09 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AWR24CS
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 1250 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps •
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- Secondary terminals under the base
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24CS Serie: CGS 248.92 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AWR24D
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2500 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24D Serie: CGS 261.04 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING
MOD: AWR24DS
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2500 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- Secondary terminals under the base
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24DS Serie: CGS 333.05 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AWR24E,F,G
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24E,F,G Serie: CGS 150.27 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AWR24H,L,M
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24H,L,M Serie: CGS 161.50 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AWR24R,S,T
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2500 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AWR24R,S,T Serie: CGS 160.08 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: NKR24/2
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: NKR24/2 Serie: BALTEAU 1500A 375.37 KB

MOD: NKR24/2 Serie: BALTEAU 3000A 354.98 KB
MOD. NKP24/2 BALTEAU SERIES
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: NKP24/2
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: NKP24/2 (3000A) IT1173X 384.46 KB

MOD: NKP24/2 2x600A 1500A IT1172X 400.77 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RCU-1
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 600 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 16 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: RCU-1 Serie: CGS 198.92 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RCU-2
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 600 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 16 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: RCU-2 Serie: CGS 208.30 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RKD24
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 300 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 150-300 A, or by secondary taps
- With two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: RKD24 Serie: BALTEAU 293.31 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RKF24
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 1200 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 400-800 A, or by secondary taps
- With two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: RKF24 Serie: BALTEAU 800A 437.03 KB

MOD: RKF24 Serie: BALTEAU 1200A 424.87 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RKH24
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 400-800 A, or by secondary taps
- With three cores
- Short time thermal current 100 Ipn/1s (max 80 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap
MOD: RKH24 Serie: BALTEAU 1500A 437.07 KBMOD: RKH24 Serie: BALTEAU 2000A 247.51 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ADR24D
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 750-1500 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1 •Protection class: 5P10 … 5P30 •The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- Dimensions in accordance with DIN 42600 Schmale Bauform
- Homologation PTB 20.21/97.53
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ADR24D Serie: DIN 364.11 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: SKG24/2
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- With three cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current Dimensions according to the DIN standard 42600 Schmale Bauform
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: SKG24/2 Serie: BALTEAU 1500A 445.64 KB

MOD: SKG24/2 Serie: BALTEAU 2000A 350.01 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RCX1
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 630 A
- Rated secondary current 5 A
- With single ratio
- With only one core
- Short time thermal current 12,5 kA/1s or 16 kA/1s
- Frequency: 50 Hz
- Enel Homologations
- Measuring class: 0,2s, 0,2; 0,5s
- Burdens: 4VA,
- Secondary terminals suitable to Enel plug DY4183/1;
- terminals in accordance with DY4390/1 specification

MOD: RCX1 Serie: CGS 186.98 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RCX1 & RCX2
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 630 A
- Rated secondary current 5 A
- With single ratio
- With only one core
- Short time thermal current 12,5 kA/1s or 16 kA/1s
- Frequency: 50 Hz
- Enel Homologations
- Measuring class: 0,2, 0,5, 1
- Burdens: 6VA, 7,5VA 10VA
- Secondary terminals suitable to Enel plug DY4183/1;
- terminals in accordance with DY4390/1 specification

MOD: RCX1 Serie: CGS 186.98 KB

MOD: RCX2 Serie: CGS 186.25 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR36L
Series: CGS
- Highest insulation level 36/70/170 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ASR36L Serie: CGS 175.66 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR36M
Series: CGS
- Highest insulation level 36/70/170 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ASR36M Serie: CGS 177.18 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: NKP36/2
Series: BALTEAU
- Highest insulation level 36/70/170 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: NKP36/2 Serie: BALTEAU 376.49 KB

NKP 36/2 3000A Serie: Balteau 358.89 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: NKR36/2
Series: BALTEAU
- Highest insulation level 36/70/170 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to three cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: NKR36/2 2x600A 1500A IT1230X 375.95 KB

MOD: NKR36/2 3000A IT1231X 364.18 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: RKF36
Serie: BALTEAU
- Highest insulation level 36/70/170 kV
- Rated primary current up to 800 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 400-800 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: RKF36 Serie: BALTEAU 429.68 KB
TRASFORMATORE DI CORRENTE TOROIDALE NASTRATO PER FUNZIONAMENTO IN BAGNO D’OLIO, PER PASSANTI TRASFORMATORI
MOD: AON A0
Serie: CGS
- Per passanti trasformatori in olio minerale
- Isolamento con carta crespata di pura cellulosa ( o con nastro cotone ) classe di isolamento 105 °C (A), quando impregnato
- Tensione di rifermento per l’isolamento 0,72/3/- kV
- Corrente nominale primaria fino a 45000 A
- Corrente nominale secondaria 5 o 1 A
- Esecuzione a singolo, doppio o multi rapporto (multi ratio) tramite prese sul secondario
- A 1 nucleo
- Corrente termica di corto circuito 100 Ipn/1s (max 150 kA/1s)
- Frequenza: 50 oppure 60 Hz
- Classi di precisione: 0,2, 0,2S, 0,5, 0,5S, 1
- Classi di protezione: 5P10 … 5P20
- I valori delle prestazioni ottenibili dipendono dalla corrente nominale primaria
- Ove richiesto esecuzione con avvolgimenti di compensazione per annullare l’influenza di campi esterni

MOD: AON A0 Serie: CGS 193.90 KB
TRASFORMATORE DI CORRENTE TOROIDALE COLATO IN RESINA
PER INTERNO, PER IMPIEGHI SPECIALI
MOD: AON-B
Serie: CGS
- Per condotti sbarre e passanti di grandi generatori elettrici
- Per montaggio su conduttori o barre isolati o opportunamente distanziate
- Tensione di rifermento per l’isolamento 0,72/3/- kV
- Corrente nominale primaria fino a 50000 A
- Corrente nominale secondaria 5 o 1 A
- Diametro interno fino a 680 mm
- Esecuzione a singolo, doppio o multi rapporto (multi ratio) tramite prese sul secondario
- Fino a 2 nuclei
- Corrente termica di corto circuito 100 Ipn/1s (max 150 kA/1s)
- Frequenza: 50 oppure 60 Hz
- Classi di precisione: 0,2, 0,2S, 0,5, 0,5S, 1
- Classi di protezione: 5P10 … 5P20
- I valori delle prestazioni ottenibili dipendono dalla corrente nominale primaria
- Ove richiesto esecuzione con avvolgimenti di compensazione per annullare l’influenza di campi esterni

MOD: AON-B Serie: CGS 143.78 KB
TRASFORMATORE DI CORRENTE TOROIDALE COLATO IN RESINA
PER INTERNO, PER IMPIEGHI SPECIALI
MOD: AON-C R
Serie: CGS
- Per condotti sbarre e passanti di grandi generatori elettrici
- Per montaggio su conduttori o barre isolati o opportunamente distanziate
- Tensione di rifermento per l’isolamento 0,72/3/- kV
- Corrente nominale primaria fino a 50000 A
- Corrente nominale secondaria 5 o 1 A
- Esecuzione a singolo, doppio o multi rapporto (multi ratio) tramite prese sul secondario
- Fino a 2 nuclei
- Corrente termica di corto circuito 100 Ipn/1s (max 150 kA/1s)
- Frequenza: 50 oppure 60 Hz
- Classi di precisione: 0,2, 0,2S, 0,5, 0,5S, 1
- Classi di protezione: 5P10 … 5P20
- I valori delle prestazioni ottenibili dipendono dalla corrente nominale primaria
- Ove richiesto esecuzione con avvolgimenti di compensazione per annullare l’influenza di campi esterni

AON-C, AON-R 161.95 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-L/06
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 300 A
- Rated secondary current 5 A
- Inner diameter 55 mm
- With single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Protection class: 5P30
- According to Enel Specification DY751/1, s/n 534006
- Available execution in accordance with CEI 0-16 Standard

AON-L/06 301.71 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-L/09
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 1250 A
- Rated secondary current 2,5-5 A
- Inner diameter 140 mm
- With double ratio by secondary taps
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring / protection class: 0,5-5P30 According to Enel Specification DY751/2, s/n 534009

AON-L/09 304.11 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-L/10
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 1600 A
- Rated secondary current 2,5-5 A
- Inner diameter 140 mm
- With double ratio by secondary taps
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring / protection class: 0,5-5P30
- According to Enel Specification DY751/3, s/n 534010

AON-L/10 275.45 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-P/02
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 100 A
- Rated secondary current 1 A
- Inner diameter 106 mm
- With single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 2VA
- According to Enel Specification DY536/1, s/n 534002

AON-P/02 355.92 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-P17/1
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 100 A
- Rated secondary current 1 A
- Inner diameter 140 mm
- With single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 2VA
- According to Enel Specification UR P017

AON-P17/1 301.07 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-P18/1
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 300 A
- Rated secondary current 5 A
- Inner diameter 140 mm
- With single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA •
- Measuring/protection class: 1-5P20 •
- According to Enel Specification UR P018/2

AON-P18/1 311.19 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-P18/2
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 600 A
- Rated secondary current 5 A
- Inner diameter 140 mm
- With single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring/protection class: 1-5P20
- According to Enel Specification UR P018/2

AON-P18/2 312.62 KB
CAST RESIN INSULATED RING CURRENT TRANSFORMER
FOR INDOOR, FOR SPECIAL PURPOSES
MOD: ORG 1 24 425 525
Series: BALTEAU
- For busducts, star points, generator circuit breakers and generator switchgears
- Internal electric shield to be connected to MV primary bar
- Highest insulation level 24/50/125 kV
- Rated primary current up to 12000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 350 mm
- External diameter 425 mm or 525 mm or 625 mm
- With one, two or multi ratio obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 150 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 …
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request execution with compensating winding to reduce the effect of external electromagnetic fields

ORG 1 24 425 525 625 275.68 KB
CAST RESIN INSULATED RING CURRENT TRANSFORMER
FOR INDOOR, FOR SPECIAL PURPOSES
MOD: ORG 1 24 750 900
Series: BALTEAU
- For busducts, star points, generator circuit breakers and generator switchgears
- Internal electric shield to be connected to MV primary bar
- Highest insulation level 24/50/125 kV
- Rated primary current up to 30000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 560 mm
- External diameter 750 or 900 mm
- With one, two or multi ratio obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 150 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request execution with compensating winding to reduce the effect of external electromagnetic fields

ORG 1 24 750 900 277.71 KB
CAST RESIN INSULATED RING CURRENT TRANSFORMER
FOR INDOOR, FOR SPECIAL PURPOSES
MOD: ORG 1 24 36 800
Series: BALTEAU
- For busducts, star points, generator circuit breakers and generator switchgears
- Internal electric shield to be connected to MV primary bar
- Highest insulation level 36/70/170 kV
- Rated primary current up to 40000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 700 mm
- External diameter 800 or 1000 mm
- With one, two or multi ratio obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 150 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request execution with compensating winding to reduce the effect of external electromagnetic fields

ORG 1 24 36 800 264.93 KB
CAST RESIN INSULATED RING CURRENT TRANSFORMER
FOR INDOOR, FOR SPECIAL PURPOSES
MOD: ORG 1 24 36 1300
Series: BALTEAU
- For busducts, star points, generator circuit breakers and generator switchgears
- Internal electric shield to be connected to MV primary bar
- Highest insulation level 36/70/170 kV
- Rated primary current up to 50000 A
- Rated secondary current 5 or 1 A
- Inner diameter 900 mm
- External diameter 1300 mm
- With one, two or multi ratio obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 150 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request execution with compensating winding to reduce the effect of external electromagnetic fields
ORG 1 24 36 1300 220.28 KB
CAST RESIN INSULATED RING CURRENT TRANSFORMER
FOR INDOOR, FOR SPECIAL PURPOSES
MOD: ORG 1 24 720
Series: BALTEAU
- For busducts, star points, generator circuit breakers and generator switchgears
- Internal electric shield to be connected to MV primary bar
- Highest insulation level 24/50/125 kV
- Rated primary current up to 10000 A
- Rated secondary current 5 or 1 A
- Inner diameter 560 mm
- External diameter 805 mm
- Mounting holes centre to centre distance: 700 mm X 700 mm
- With one, two or multi ratio obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 150 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request execution with compensating winding to reduce the effect of external electromagnetic fields

ORG 1 24 720 277.71 KB
CAST RESIN INSULATED RING CURRENT TRANSFORMER
FOR INDOOR, FOR SPECIAL PURPOSES
MOD: ORG 1 24 805
Series: BALTEAU
- For busducts, star points, generator circuit breakers and generator switchgears
- Internal electric shield to be connected to MV primary bar
- Highest insulation level 24/50/125 kV
- Rated primary current up to 30000 A
- Rated secondary current 5 or 1 A
- Inner diameter 560 mm
- External diameter 805 mm
- Mounting holes centre to centre distance: 700 mm X 700 mm
- With one, two or multi ratio obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 150 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request execution with compensating winding to reduce the effect of external electromagnetic fields

ORG 1 24 805 300.54 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: AOR12B
Series: CGS
- Highest insulation level 12/28/75 kV
- Electric shield to be connected to MV primary bar
- Rated primary current up to 5000 A
- Rated secondary current 5 or 1 A
- Inner diameter 124 mm
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AOR12B Serie: CGS 42.22 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: AOR12C
Series: CGS
- Highest insulation level 12/28/75 kV
- Electric shield to be connected to MV primary bar
- Rated primary current up to 5000 A
- Rated secondary current 5 or 1 A
- Inner diameter 115 mm
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AOR12C Serie: CGS 42.59 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: AOR24B
Series: CGS
- Highest insulation level 24/50/125 kV
- Electric shield to be connected to MV primary bar
- Rated primary current up to 5000 A
- Rated secondary current 5 or 1 A
- Inner diameter 124 mm
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: AOR24B Serie: CGS 46.65 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: IRM12/2
Series: BALTEAU
- Highest insulation level 12/28/75 kV
- Internal electric shield to be connected to MV primary bar
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- Inner diameter 58 mm
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 60 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: IRM12/2 Serie: BALTEAU 42.01 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: IRM17/2
Series: BALTEAU
- Highest insulation level 17,5/38/95 kV
- Internal electric shield to be connected to MV primary bar
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 120 mm
- With one or two ratios obtained by secondary taps
- Up to five cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: IRM17/2 Serie: BALTEAU 29.18 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: IRM24/2
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 120 mm
- With one or two ratios obtained by secondary taps
- Up to five cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: IRM24/2 Serie: BALTEAU 27.65 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: IRN24/2
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Internal electric shield to be connected to MV primary bar
- Rated primary current up to 5000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 150 mm
- With one or two ratios obtained by secondary taps
- Up to five cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: IRN17/2 Serie: BALTEAU 29.67 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: IRM36
Series: BALTEAU
- Highest insulation level 36/70/170 kV
- Internal electric shield to be connected to MV primary bar
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 120 mm
- With one or two ratios obtained by secondary taps
- Up to five cores •Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: IRM36 Serie: BALTEAU 23.04 KB
INDOOR CURRENT TRANSFORMER RESIN INSULATED
WINDOW TYPE
MOD: IRN36
Series: BALTEAU
- Highest insulation level 36/70/170 kV
- Internal electric shield to be connected to MV primary bar
- Rated primary current up to 5000 A
- Rated secondary current 5 or 1 A
- Inner diameter up to 120 mm
- With one or two ratios obtained by secondary taps
- Up to five cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: IRN36 Serie: BALTEAU 25.38 KB
OUTDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR24AA
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 600 A
- Rated secondary current 5 or 1 A
- With single ratio
- With only one core
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: ASR24AA Serie: CGS 238.72 KB
OUTDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR24BA
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: ASR24BA Serie: CGS 275.63 KB
OUTDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: ASR36BA
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 3000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: ASR36BA Serie: CGS 203.47 KB
OUTDOOR CURRENT TRANSFORMER RESIN INSULATED
WITH PRIMARY WINDING
MOD: AON-BE IT2001XC
Series: CGS
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s (max 40 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AON-B IT2001XC Serie: CGS 203.47 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-BE IT2564X
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 4000 A
- Rated secondary current 5 or 1 A
- Inner diameter 210 mm
- With one or two ratios obtained by secondary taps
- One core
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AON-BE IT2564X Serie: CGS 176.49 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-BE IT3179XB
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 2000 A
- Rated secondary current 5 or 1 A
- Inner diameter 113 mm
- With one or two ratios obtained by secondary taps
- One core
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AON-B IT3179XB Serie: CGS 15.17 KB
V.max insul. 0,72 kV
I pn max 300 A
Øint 55mm
cast resin
MOD: AON L IT2229XA
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 300 A
- Rated secondary current 5 or 1 A
- Inner diameter 55 mm
- With one or two ratios obtained by secondary taps
- One core
- Short time thermal current 100 Ipn/1s (max 16 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AON L IT2229XA Serie: CGS 14.98 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: BER/2
Series: BALTEAU
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 750 A
- Rated secondary current 5 A
- Inner diameter up to 115 mm
- With one or two ratios obtained by secondary taps
- Up to four cores
- Short time thermal current 100 Ipn/1s (max 100 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: mounting brackets

MOD: BER/2 Serie: BALTEAU 17.57 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-PE/1
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 750 A
- Rated secondary current 5 A
- Inner diameter 106 mm
- Single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring class / Saturation factor: 0,2 / FS10
- According to Enel Specific DY38/1, s/n 534020

MOD: AON-PE/1 Serie: CGS 17.64 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-PE/2
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 1500 A
- Rated secondary current 5 A
- Inner diameter 140 mm
- Single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring class / Saturation factor: 0,2 / FS10
- According to Enel DY38/2, s/n 534021v

MOD: AON-PE/2 Serie: CGS 20.07 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-PE/3
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 3000 A
- Rated secondary current 5 A
- Inner diameter 140 mm
- Single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring class / Saturation factor: 0,2 / FS10
- According to Enel Specific DY38/3, s/n 534022

MOD: BER/2 Serie: BALTEAU 17.57 KB
CAST RESIN RING CORE CURRENT TRANSFORMER
FOR INDOOR, FOR MV CABLES
MOD: AON-PE/4
Series: CGS
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 3000 A
- Rated secondary current 5 A
- Inner diameter 140 mm
- Single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 10VA
- Measuring class / Saturation factor: 0,2 / FS10
- According to Enel Specific DY38/4, s/n 534023

MOD: AON-PE/4 Serie: CGS 20.55 KB
INDOOR SPLIT CORE CURRENT TRANSFORMER
RESIN INSULATED
MOD: AQR-F
Series: CGS
- Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 1200 A
- Rated secondary current 1 or 5 A
- Inner diameter 100 mm
- With one, two or multi ratio obtained by secondary taps
- One core
- Short time thermal current 100 Ipn/1s (max 20 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AQR-F Serie: CGS 19.37 KB
INDOOR SPLIT CORE CURRENT TRANSFORMER
RESIN INSULATED
MOD: AQR-L
Series: CGS
- Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 1000 A
- Rated secondary current 1 or 5 A
- Inner diameter 106 mm
- With one, two or multi ratio obtained by secondary taps
- One core
- Short time thermal current 100 Ipn/1s (max 20 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AQR-L Serie: CGS 20.33 KB
OUTDOOR SPLIT CORE CURRENT TRANSFORMER
RESIN INSULATED
MOD: AQR-LE
Series: CGS
- Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current up to 1000 A
- Rated secondary current 1 or 5 A
- Inner diameter 106 mm
- With one, two or multi ratio obtained by secondary taps
- One core
- Short time thermal current 100 Ipn/1s (max 20 kA/1s)
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10 … 5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current

MOD: AQR-LE Serie: CGS 29.29 KB
INDOOR SPLIT CORE CURRENT TRANSFORMER
RESIN INSULATED
MOD: AQR-L/03
Series: CGS
- Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
- To be mounted on MV insulated cables
- Highest insulation level 0,72/3/- kV
- Rated primary current 100 A
- Rated secondary current 1 A
- Inner diameter 106 mm
- Single ratio
- One core
- Short time thermal current 12,5 kA/1s
- Frequency: 50 Hz
- Burden: 2VA
- According to Enel specific DY536/2, s/n 534003

MOD: AQR-L/03 Serie: CGS 29.29 KB
INDOOR THREE-PHASE CURRENT TRANSFORMER RESIN INSULATED
MOD: ATR12B
Series: CGS
- Highest insulation level 12/28/75 kV
- Rated primary current up to 400 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 80 Ipn/1s
- Frequency: 50 or 60 Hz
- Measuring class : 1
- Protection class: 5P10
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- On request: 3 or only 2 active phases
- On request: sealable cover on secondary terminals
- On request: capacitive tap

MOD: ATR12B Serie: CGS 42.01 KB
METALISED INDOOR SINGLE-PHASE CURRENT TRANSFORMER RESIN INSULATED WITH OUTER CONE
MOD: ADR24D-C
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary current up to 300 A
- Rated secondary current 5 or 1 A
- With one or two ratios obtained by secondary taps
- Up to two cores
- Short time thermal current 100 Ipn/1s
- Frequency: 50 or 60 Hz
- Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
- Protection class: 5P10...5P30
- The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
- Primary terminals with external cone, cable plug in EN 50181 type A
- On request: sealable cover on secondary terminals
- On request: capacitive tap

ADR24D-C IT4312XB 288.84 KB