CURRENT TRANSFORMERS

CT with primary winding or
with primary bar or
ring CT
IEC 61869 standards or, on request, others (ANSI, CSA….)
For indoor or for outdoor
Insulation up to 41,5 kV
Primary current up to 50000 A
Secondary current 5 A or 1 A
Short time thermal current up to 100 KA/1s
Accuracy class up to Cl. 0,1

INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING Mod: ADR17C Series: CGS
  • Highest insulation level 17,5/38/95 kV
  • Rated primary current up to 2500 A
  • Rated secondary current 5 or 1 A
  • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
  • Up to three cores
  • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
  • Frequency: 50 or 60 Hz
  • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
  • Protection class: 5P10 … 5P30
  • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • Homologation PTB 20.21/97.53
  • On request: sealable cover on secondary terminals
  • On request: capacitive tap
INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ADR17E Series: CGS
  • Highest insulation level 17,5/38/95 kV
  • Rated primary current up to 3000 A
  • Rated secondary current 5 or 1 A
  • With one or two ratios obtained by secondary taps
  • Up to three cores
  • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
  • Frequency: 50 or 60 Hz
  • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
  • Protection class: 5P10 … 5P30
  • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
  • On request: sealable cover on secondary terminals
  • On request: capacitive tap
INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY BAR MOD: AWR17J Series: CGS
  • Highest insulation level 17,5/38/95 kV
  • Rated primary current up to 2500 A
  • Rated secondary current 5 or 1 A
  • With one or two ratios obtained by secondary taps
  • Up to three cores
  • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
  • Frequency: 50 or 60 Hz
  • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
  • Protection class: 5P10 … 5P30
  • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
  • On request: sealable cover on secondary terminals
  • On request: capacitive tap
INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY BAR MOD: AWR12E Series: CGS
  • Highest insulation level 12/28/75 kV
  • Rated primary current up to 2000 A
  • Rated secondary current 5 or 1 A
  • With one or two ratios obtained by secondary taps
  • Up to two cores
  • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
  • Frequency: 50 or 60 Hz
  • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
  • Protection class: 5P10 … 5P30
  • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
  • On request: sealable cover on secondary terminals
  • On request: capacitive tap
INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY BAR MOD: AWR17H Series: CGS
  • Highest insulation level 17,5/38/95 kV
  • Rated primary current up to 2500 A
  • Rated secondary current 5 or 1 A
  • With one or two ratios obtained by secondary taps
  • Up to three cores
  • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
  • Frequency: 50 or 60 Hz
  • According to IEC 60044-1; other Standards (ANSI, CSA…) on request
  • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
  • Protection class: 5P10 … 5P30
  • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
  • On request: sealable cover on secondary terminals
  • On request: capacitive tap
  • INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: SKG17/2 Series: BALTEAU
    • Highest insulation level 17,5/38/95 kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • Dimensions in accordance with DIN 42600 Schmale Bauform
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RKC12 Series: BALTEAU
    • Highest insulation level 12/28/75 kV
    • Rated primary current up to 100 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 16 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR24D Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 600 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
    • With only one core
    • Short time thermal current 100 Ipn/1s (max 30 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR24E Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 600 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 30 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY BAR MOD: AWR24B Series: CGS
    • Highest insulation level 24/50/125
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24C Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 1250 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24CS Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 1250 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps •
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • Secondary terminals under the base
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24D Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2500 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24DS Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2500 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • Secondary terminals under the base
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24E,F,G Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24H,L,M Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AWR24R,S,T Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2500 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: NKR24/2 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    MOD. NKP24/2 BALTEAU SERIES INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: NKP24/2 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RCU-1 Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 600 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 16 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RCU-2 Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 600 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 16 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RKD24 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 300 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 150-300 A, or by secondary taps
    • With two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RKF24 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 1200 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 400-800 A, or by secondary taps
    • With two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RKH24 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 400-800 A, or by secondary taps
    • With three cores
    • Short time thermal current 100 Ipn/1s (max 80 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ADR24D Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 750-1500 A, or by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1 •Protection class: 5P10 … 5P30 •The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • Dimensions in accordance with DIN 42600 Schmale Bauform
    • Homologation PTB 20.21/97.53
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: SKG24/2 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • With three cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • Dimensions according to the DIN standard 42600 Schmale Bauform
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RCX1 Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 630 A
    • Rated secondary current 5 A
    • With single ratio
    • With only one core
    • Short time thermal current 12,5 kA/1s or 16 kA/1s
    • Frequency: 50 Hz
    • Enel Homologations
    • Measuring class: 0,2s, 0,2; 0,5s
    • Burdens: 4VA,
    • Secondary terminals suitable to Enel plug DY4183/1;
    • terminals in accordance with DY4390/1 specification
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RCX1 & RCX2 Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 630 A
    • Rated secondary current 5 A
    • With single ratio
    • With only one core
    • Short time thermal current 12,5 kA/1s or 16 kA/1s
    • Frequency: 50 Hz
    • Enel Homologations
    • Measuring class: 0,2, 0,5, 1
    • Burdens: 6VA, 7,5VA 10VA
    • Secondary terminals suitable to Enel plug DY4183/1;
    • terminals in accordance with DY4390/1 specification
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR36L Series: CGS
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR36M Series: CGS
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 300-600 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: NKP36/2 Series: BALTEAU
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: NKR36/2 Series: BALTEAU
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to three cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: RKF36 Serie: BALTEAU
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 800 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 400-800 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    TRASFORMATORE DI CORRENTE TOROIDALE NASTRATO PER FUNZIONAMENTO IN BAGNO D’OLIO, PER PASSANTI TRASFORMATORI MOD: AON A0 Serie: CGS
    • Per passanti trasformatori in olio minerale
    • Isolamento con carta crespata di pura cellulosa ( o con nastro cotone ) classe di isolamento 105 °C (A), quando impregnato
    • Tensione di rifermento per l’isolamento 0,72/3/- kV
    • Corrente nominale primaria fino a 45000 A
    • Corrente nominale secondaria 5 o 1 A
    • Esecuzione a singolo, doppio o multi rapporto (multi ratio) tramite prese sul secondario
    • A 1 nucleo
    • Corrente termica di corto circuito 100 Ipn/1s (max 150 kA/1s)
    • Frequenza: 50 oppure 60 Hz
    • Classi di precisione: 0,2, 0,2S, 0,5, 0,5S, 1
    • Classi di protezione: 5P10 … 5P20
    • I valori delle prestazioni ottenibili dipendono dalla corrente nominale primaria
    • Ove richiesto esecuzione con avvolgimenti di compensazione per annullare l’influenza di campi esterni
    TRASFORMATORE DI CORRENTE TOROIDALE COLATO IN RESINA PER INTERNO, PER IMPIEGHI SPECIALI MOD: AON-B Serie: CGS
    • Per condotti sbarre e passanti di grandi generatori elettrici
    • Per montaggio su conduttori o barre isolati o opportunamente distanziate
    • Tensione di rifermento per l’isolamento 0,72/3/- kV
    • Corrente nominale primaria fino a 50000 A
    • Corrente nominale secondaria 5 o 1 A
    • Diametro interno fino a 680 mm
    • Esecuzione a singolo, doppio o multi rapporto (multi ratio) tramite prese sul secondario
    • Fino a 2 nuclei
    • Corrente termica di corto circuito 100 Ipn/1s (max 150 kA/1s)
    • Frequenza: 50 oppure 60 Hz
    • Classi di precisione: 0,2, 0,2S, 0,5, 0,5S, 1
    • Classi di protezione: 5P10 … 5P20
    • I valori delle prestazioni ottenibili dipendono dalla corrente nominale primaria
    • Ove richiesto esecuzione con avvolgimenti di compensazione per annullare l’influenza di campi esterni
    TRASFORMATORE DI CORRENTE TOROIDALE COLATO IN RESINA PER INTERNO, PER IMPIEGHI SPECIALI MOD: AON-C R Serie: CGS
    • Per condotti sbarre e passanti di grandi generatori elettrici
    • Per montaggio su conduttori o barre isolati o opportunamente distanziate
    • Tensione di rifermento per l’isolamento 0,72/3/- kV
    • Corrente nominale primaria fino a 50000 A
    • Corrente nominale secondaria 5 o 1 A
    • Esecuzione a singolo, doppio o multi rapporto (multi ratio) tramite prese sul secondario
    • Fino a 2 nuclei
    • Corrente termica di corto circuito 100 Ipn/1s (max 150 kA/1s)
    • Frequenza: 50 oppure 60 Hz
    • Classi di precisione: 0,2, 0,2S, 0,5, 0,5S, 1
    • Classi di protezione: 5P10 … 5P20
    • I valori delle prestazioni ottenibili dipendono dalla corrente nominale primaria
    • Ove richiesto esecuzione con avvolgimenti di compensazione per annullare l’influenza di campi esterni
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-L/06 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 300 A
    • Rated secondary current 5 A
    • Inner diameter 55 mm
    • With single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Protection class: 5P30
    • According to Enel Specification DY751/1, s/n 534006
    • Available execution in accordance with CEI 0-16 Standard
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-L/09 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 1250 A
    • Rated secondary current 2,5-5 A
    • Inner diameter 140 mm
    • With double ratio by secondary taps
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring / protection class: 0,5-5P30 According to Enel Specification DY751/2, s/n 534009
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-L/10 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 1600 A
    • Rated secondary current 2,5-5 A
    • Inner diameter 140 mm
    • With double ratio by secondary taps
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring / protection class: 0,5-5P30
    • According to Enel Specification DY751/3, s/n 534010
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-P/02 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 100 A
    • Rated secondary current 1 A
    • Inner diameter 106 mm
    • With single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 2VA
    • According to Enel Specification DY536/1, s/n 534002
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-P17/1 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 100 A
    • Rated secondary current 1 A
    • Inner diameter 140 mm
    • With single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 2VA
    • According to Enel Specification UR P017
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-P18/1 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 300 A
    • Rated secondary current 5 A
    • Inner diameter 140 mm
    • With single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA •
    • Measuring/protection class: 1-5P20 •
    • According to Enel Specification UR P018/2
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-P18/2 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 600 A
    • Rated secondary current 5 A
    • Inner diameter 140 mm
    • With single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring/protection class: 1-5P20
    • According to Enel Specification UR P018/2
    CAST RESIN INSULATED RING CURRENT TRANSFORMER FOR INDOOR, FOR SPECIAL PURPOSES MOD: ORG 1 24 425 525 Series: BALTEAU
    • For busducts, star points, generator circuit breakers and generator switchgears
    • Internal electric shield to be connected to MV primary bar
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 12000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 350 mm
    • External diameter 425 mm or 525 mm or 625 mm
    • With one, two or multi ratio obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 150 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 …
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request execution with compensating winding to reduce the effect of external electromagnetic fields
    CAST RESIN INSULATED RING CURRENT TRANSFORMER FOR INDOOR, FOR SPECIAL PURPOSES MOD: ORG 1 24 750 900 Series: BALTEAU
    • For busducts, star points, generator circuit breakers and generator switchgears
    • Internal electric shield to be connected to MV primary bar
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 30000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 560 mm
    • External diameter 750 or 900 mm
    • With one, two or multi ratio obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 150 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request execution with compensating winding to reduce the effect of external electromagnetic fields
    CAST RESIN INSULATED RING CURRENT TRANSFORMER FOR INDOOR, FOR SPECIAL PURPOSES MOD: ORG 1 24 36 800 Series: BALTEAU
    • For busducts, star points, generator circuit breakers and generator switchgears
    • Internal electric shield to be connected to MV primary bar
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 40000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 700 mm
    • External diameter 800 or 1000 mm
    • With one, two or multi ratio obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 150 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request execution with compensating winding to reduce the effect of external electromagnetic fields
    CAST RESIN INSULATED RING CURRENT TRANSFORMER FOR INDOOR, FOR SPECIAL PURPOSES MOD: ORG 1 24 36 1300 Series: BALTEAU
    • For busducts, star points, generator circuit breakers and generator switchgears
    • Internal electric shield to be connected to MV primary bar
    • Highest insulation level 36/70/170 kV
    • Rated primary current up to 50000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 900 mm
    • External diameter 1300 mm
    • With one, two or multi ratio obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 150 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request execution with compensating winding to reduce the effect of external electromagnetic fields
    CAST RESIN INSULATED RING CURRENT TRANSFORMER FOR INDOOR, FOR SPECIAL PURPOSES MOD: ORG 1 24 720 Series: BALTEAU
    • For busducts, star points, generator circuit breakers and generator switchgears
    • Internal electric shield to be connected to MV primary bar
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 10000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 560 mm
    • External diameter 805 mm
    • Mounting holes centre to centre distance: 700 mm X 700 mm
    • With one, two or multi ratio obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 150 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request execution with compensating winding to reduce the effect of external electromagnetic fields
    CAST RESIN INSULATED RING CURRENT TRANSFORMER FOR INDOOR, FOR SPECIAL PURPOSES MOD: ORG 1 24 805 Series: BALTEAU
    • For busducts, star points, generator circuit breakers and generator switchgears
    • Internal electric shield to be connected to MV primary bar
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 30000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 560 mm
    • External diameter 805 mm
    • Mounting holes centre to centre distance: 700 mm X 700 mm
    • With one, two or multi ratio obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 150 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request execution with compensating winding to reduce the effect of external electromagnetic fields
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: AOR12B Series: CGS
    • Highest insulation level 12/28/75 kV
    • Electric shield to be connected to MV primary bar
    • Rated primary current up to 5000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 124 mm
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: AOR12C Series: CGS
    • Highest insulation level 12/28/75 kV
    • Electric shield to be connected to MV primary bar
    • Rated primary current up to 5000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 115 mm
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: AOR24B Series: CGS
    • Highest insulation level 24/50/125 kV
    • Electric shield to be connected to MV primary bar
    • Rated primary current up to 5000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 124 mm
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: IRM12/2 Series: BALTEAU
    • Highest insulation level 12/28/75 kV
    • Internal electric shield to be connected to MV primary bar
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 58 mm
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 60 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: IRM17/2 Series: BALTEAU
    • Highest insulation level 17,5/38/95 kV
    • Internal electric shield to be connected to MV primary bar
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 120 mm
    • With one or two ratios obtained by secondary taps
    • Up to five cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: IRM24/2 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 120 mm
    • With one or two ratios obtained by secondary taps
    • Up to five cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: IRN24/2 Series: BALTEAU
    • Highest insulation level 24/50/125 kV
    • Internal electric shield to be connected to MV primary bar
    • Rated primary current up to 5000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 150 mm
    • With one or two ratios obtained by secondary taps
    • Up to five cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: IRM36 Series: BALTEAU
    • Highest insulation level 36/70/170 kV
    • Internal electric shield to be connected to MV primary bar
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 120 mm
    • With one or two ratios obtained by secondary taps
    • Up to five cores •Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    INDOOR CURRENT TRANSFORMER RESIN INSULATED WINDOW TYPE MOD: IRN36 Series: BALTEAU
    • Highest insulation level 36/70/170 kV
    • Internal electric shield to be connected to MV primary bar
    • Rated primary current up to 5000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter up to 120 mm
    • With one or two ratios obtained by secondary taps
    • Up to five cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    OUTDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR24AA Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 600 A
    • Rated secondary current 5 or 1 A
    • With single ratio
    • With only one core
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    OUTDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR24BA Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    OUTDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: ASR36BA Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 3000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    OUTDOOR CURRENT TRANSFORMER RESIN INSULATED WITH PRIMARY WINDING MOD: AON-BE IT2001XC Series: CGS
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by primary reconnection up to 600-1200 A, or by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s (max 40 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-BE IT2564X Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 4000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 210 mm
    • With one or two ratios obtained by secondary taps
    • One core
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-BE IT3179XB Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 2000 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 113 mm
    • With one or two ratios obtained by secondary taps
    • One core
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    V.max insul. 0,72 kV I pn max 300 A Øint 55mm cast resin MOD: AON L IT2229XA Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 300 A
    • Rated secondary current 5 or 1 A
    • Inner diameter 55 mm
    • With one or two ratios obtained by secondary taps
    • One core
    • Short time thermal current 100 Ipn/1s (max 16 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: BER/2 Series: BALTEAU
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 750 A
    • Rated secondary current 5 A
    • Inner diameter up to 115 mm
    • With one or two ratios obtained by secondary taps
    • Up to four cores
    • Short time thermal current 100 Ipn/1s (max 100 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: mounting brackets
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-PE/1 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 750 A
    • Rated secondary current 5 A
    • Inner diameter 106 mm
    • Single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring class / Saturation factor: 0,2 / FS10
    • According to Enel Specific DY38/1, s/n 534020
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-PE/2 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 1500 A
    • Rated secondary current 5 A
    • Inner diameter 140 mm
    • Single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring class / Saturation factor: 0,2 / FS10
    • According to Enel DY38/2, s/n 534021v
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-PE/3 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 3000 A
    • Rated secondary current 5 A
    • Inner diameter 140 mm
    • Single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring class / Saturation factor: 0,2 / FS10
    • According to Enel Specific DY38/3, s/n 534022
    CAST RESIN RING CORE CURRENT TRANSFORMER FOR INDOOR, FOR MV CABLES MOD: AON-PE/4 Series: CGS
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 3000 A
    • Rated secondary current 5 A
    • Inner diameter 140 mm
    • Single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 10VA
    • Measuring class / Saturation factor: 0,2 / FS10
    • According to Enel Specific DY38/4, s/n 534023
    INDOOR SPLIT CORE CURRENT TRANSFORMER RESIN INSULATED MOD: AQR-F Series: CGS
    • Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 1200 A
    • Rated secondary current 1 or 5 A
    • Inner diameter 100 mm
    • With one, two or multi ratio obtained by secondary taps
    • One core
    • Short time thermal current 100 Ipn/1s (max 20 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    INDOOR SPLIT CORE CURRENT TRANSFORMER RESIN INSULATED MOD: AQR-L Series: CGS
    • Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 1000 A
    • Rated secondary current 1 or 5 A
    • Inner diameter 106 mm
    • With one, two or multi ratio obtained by secondary taps
    • One core
    • Short time thermal current 100 Ipn/1s (max 20 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    OUTDOOR SPLIT CORE CURRENT TRANSFORMER RESIN INSULATED MOD: AQR-LE Series: CGS
    • Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current up to 1000 A
    • Rated secondary current 1 or 5 A
    • Inner diameter 106 mm
    • With one, two or multi ratio obtained by secondary taps
    • One core
    • Short time thermal current 100 Ipn/1s (max 20 kA/1s)
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10 … 5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    INDOOR SPLIT CORE CURRENT TRANSFORMER RESIN INSULATED MOD: AQR-L/03 Series: CGS
    • Particularly used in detecting homopolar currents on three-phase cables for the directional earth fault protection
    • To be mounted on MV insulated cables
    • Highest insulation level 0,72/3/- kV
    • Rated primary current 100 A
    • Rated secondary current 1 A
    • Inner diameter 106 mm
    • Single ratio
    • One core
    • Short time thermal current 12,5 kA/1s
    • Frequency: 50 Hz
    • Burden: 2VA
    • According to Enel specific DY536/2, s/n 534003
    INDOOR THREE-PHASE CURRENT TRANSFORMER RESIN INSULATED MOD: ATR12B Series: CGS
    • Highest insulation level 12/28/75 kV
    • Rated primary current up to 400 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 80 Ipn/1s
    • Frequency: 50 or 60 Hz
    • Measuring class : 1
    • Protection class: 5P10
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • On request: 3 or only 2 active phases
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap
    METALISED INDOOR SINGLE-PHASE CURRENT TRANSFORMER RESIN INSULATED WITH OUTER CONE MOD: ADR24D-C Series: CGS
    • Highest insulation level 24/50/125 kV
    • Rated primary current up to 300 A
    • Rated secondary current 5 or 1 A
    • With one or two ratios obtained by secondary taps
    • Up to two cores
    • Short time thermal current 100 Ipn/1s
    • Frequency: 50 or 60 Hz
    • Measuring class : 0,2, 0,2S, 0,5, 0,5S, 1
    • Protection class: 5P10...5P30
    • The obtainable burdens depend on the ratio between rated short time thermal current and rated primary current
    • Primary terminals with external cone, cable plug in EN 50181 type A
    • On request: sealable cover on secondary terminals
    • On request: capacitive tap