Voltage Transformers

Single pole VTs for phase to earth connection
Double poles VTs for phase to phase connection
IEC 61869 standards or, on request, others (ANSI, CSA…)
For indoor or for outdoor
Highest system voltage up to 52 kV
Primary voltage up to 45000:V3 V or 33000 V
Secondary voltage 100 V, 110 V, 100:V3 V, 110:V3 V
Accuracy class up to Cl. 0,1

INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: EDR17C Series: DIN
  • Highest insulation level 17,5/38/95 kV
  • Rated primary voltage up to 15000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • Different characteristics upon agreement
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: ESR17C Series: CGS
  • Highest insulation level 17,5/38/95 kV
  • Rated primary voltage up to 15000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 10VA/Cl.0,2 - 30VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH HORIZONTAL BUILT-IN FUSEHOLDER MOD: EVR17C Series: CGS
  • Highest insulation level 17,5/38/95 kV
  • Rated primary voltage up to 15000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 10VA/Cl.0,2 - 30VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKP12/2 Series: BALTEAU
  • Highest insulation level 17,5/38/95 kV
  • Rated primary voltage up to 15000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 15VA/Cl.0,2 - 50VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 300 VA
  • Different characteristics upon agreement
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: EDR24D Series: DIN
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Available execution in accordance with CEI 0-16
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: ESR24D Series: CGS
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Available execution in accordance with CEI 0-16
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: ESR24L SerieS: CGS
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • According to CIMEC prescription and CEI- UNEL 21807 specification from 12 up to 24 kV
  • Homologated Enel DY541/1, UR P001
  • Available execution in accordance with CEI 0-16
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH HORIZONTAL BUILT-IN FUSEHOLDER MOD: EVR24D Series: CGS
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Suitable to 24kV 2A fuses
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKM24/2 Series: BALTEAU
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V; rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Available execution in accordance with CEI 0-16
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKM24/3 Series: BALTEAU
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Available execution in accordance with CEI 0-16
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKP24/2 Series: BALTEAU
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 20000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • Different characteristics upon agreement
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKP24/3 Series: BALTEAU
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 20000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH VERTICAL BUILT-IN FUSEHOLDER MOD: UR2-18F Series: BALTEAU
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 20000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • ypical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • Different characteristics upon agreement
  • Suitable to 24kV 6,3A fuses
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: ESR36D Series: CGS
  • Highest insulation level 36/70/170 Kv
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 800 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: ESR36L Series: CGS
  • Highest insulation level 36/70/170 Kv
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 800 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKH36 Series: BALTEAU
  • Highest insulation level 36/70/170 Kv
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 30VA/Cl.0,2 - 90VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 350 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKM36 Series: BALTEAU
  • Highest insulation level 36/70/170 kV
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 75VA/Cl.0,2 - 200VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 800 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH VERTICAL BUILT-IN FUSEHOLDER MOD: UR3-18F Series: BALTEAU
  • Highest insulation level 36/70/170 Kv
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings; with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h; frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Suitable to 36kV 6,3A fuses
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH VERTICAL BUILT-IN FUSEHOLDER MOD: UR3-18F/2 Series: BALTEAU
  • Highest insulation level 36/70/170 Kv
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 70VA/Cl.0,2 - 180VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 800 VA
  • Different characteristics upon agreement
  • Suitable to 36kV 6,3A fuses
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: UKM52 Series: BALTEAU
  • Highest insulation level 52/95/250 kV
  • Rated primary voltage up to 45000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 70VA/Cl.0,2 - 180VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 800 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VDR12C Series: DIN
  • Highest insulation level 12/28/75 kV
  • Rated primary voltage up to 11000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 30VA/Cl.0,2 - 80VA/Cl.0,5
  • Maximum thermal burden: 450 VA
  • Different characteristics upon agreement
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VDR24D Series: DIN
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 23000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • Dimensions in accordance with DIN 42600 Schmale Bauform
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VKP24/2 Series: BALTEAU
  • Highest insulation level 17,5/38/95 kV
  • Rated primary voltage up to 15000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 30VA/Cl.0,2 - 80VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VSR24D Series: CGS
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 23000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VSR24F Series: CGS
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 22000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VSR24L Series: CGS
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 22000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • According to CIMEC prescription and CEI- UNEL 21807 specification from 12 up to 24 kV
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VKM 24 2 H Series: BALTEAU
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 23000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VKM36 Series: BALTEAU
  • Highest insulation level 36/70/170 kV
  • Rated primary voltage up to 33000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 75VA/Cl.0,2 - 200VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED PHASE TO PHASE CONNECTION MOD: VSR36L Series: CGS
  • Highest insulation level 36/70/170 kV
  • Rated primary voltage up to 33000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 75VA/Cl.0,2 - 200VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
  • On request: sealable cover on secondary terminals
OUTDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: URE24 Series: CGS
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h; frequency 50 or 60 Hz
  • Typical performances: 20VA/Cl.0,2 - 50VA/Cl.0,5;
  • tertiary 30VA/Cl.3P
  • Maximum thermal burden: 400 VA
  • Different characteristics upon agreement
OUTDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION MOD: URE36 Series: CGS
  • Highest insulation level 36/70/170 kV
  • Rated primary voltage up to 33000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
OUTDOOR VOLTAGE TRANSFORMER DOUBLE POLES INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VRE24 Series: CGS
  • Highest insulation level 24/50/125 kV
  • Rated primary voltage up to 23000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 20VA/Cl.0,2 - 50VA/Cl.0,5
  • Maximum thermal burden: 400 VA
  • Different characteristics upon agreement
OUTDOOR VOLTAGE TRANSFORMER DOUBLE POLES INSULATED, FOR PHASE TO PHASE CONNECTION MOD: VRE36 Series: CGS
  • Highest insulation level 36/70/170 kV
  • Rated primary voltage up to 33000 V;
  • rated secondary voltage 100 V or 110 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Voltage factor 1,2 Un/cont.;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5
  • Maximum thermal burden: 600 VA
  • Different characteristics upon agreement
VOLTAGE TRANSFORMER WITH METALLIZED EXECUTION SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH OUTER CONE MOD: EDR24CE
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 200 VA
  • Different characteristics upon agreement
  • Primary terminal with external cone, cable plug in EN 50181 type A
  • On request: sealable cover on secondary terminals
VOLTAGE TRANSFORMER RESIN INSULATED WITH METALLIZED EXECUTION SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH OUTER CONE MOD: EDR24DE
  • Highest insulation level 24/50/125 Kv
  • Rated primary voltage up to 23000:V3 V;
  • rated secondary voltage 100:V3 V or 110:V3 V
  • With one or two secondary windings;
  • with one or two ratios obtained by secondary taps
  • Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
  • Voltage factor 1,9 Un/8h;
  • frequency 50 or 60 Hz
  • Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
  • tertiary 50VA/Cl.3P
  • Maximum thermal burden: 500 VA
  • Different characteristics upon agreement
  • Primary terminal with external cone, cable plug in EN 50181 type A
  • Available execution in accordance with CEI 0-16 2012-12
  • On request: sealable cover on secondary terminals