Voltage Transformers
Single pole VTs for phase to earth connection
Double poles VTs for phase to phase connection
IEC 61869 standards or, on request, others (ANSI, CSA…)
For indoor or for outdoor
Highest system voltage up to 52 kV
Primary voltage up to 45000:V3 V or 33000 V
Secondary voltage 100 V, 110 V, 100:V3 V, 110:V3 V
Accuracy class up to Cl. 0,1

PTs Selection guide 1.37 MB

INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: EDR17C
Series: DIN
- Highest insulation level 17,5/38/95 kV
- Rated primary voltage up to 15000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- Different characteristics upon agreement
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: EDR17C Serie: DIN 30.01 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: ESR17C
Series: CGS
- Highest insulation level 17,5/38/95 kV
- Rated primary voltage up to 15000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 10VA/Cl.0,2 - 30VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- On request: sealable cover on secondary terminals

MOD: ESR17C Serie: CGS 24.78 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
WITH HORIZONTAL BUILT-IN FUSEHOLDER
MOD: EVR17C
Series: CGS
- Highest insulation level 17,5/38/95 kV
- Rated primary voltage up to 15000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 10VA/Cl.0,2 - 30VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- On request: sealable cover on secondary terminals

MOD: EVR17C Serie: CGS 29.74 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKP12/2
Series: BALTEAU
- Highest insulation level 17,5/38/95 kV
- Rated primary voltage up to 15000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 15VA/Cl.0,2 - 50VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 300 VA
- Different characteristics upon agreement
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: UKP12/2 Serie: BALTEAU 34.27 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: EDR24D
Series: DIN
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Available execution in accordance with CEI 0-16
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: EDR24D Serie: DIN 24.34 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: ESR24D
Series: CGS
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Available execution in accordance with CEI 0-16
- On request: sealable cover on secondary terminals

MOD: ESR24D Serie: CGS 13.54 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: ESR24L
SerieS: CGS
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- According to CIMEC prescription and CEI- UNEL 21807 specification from 12 up to 24 kV
- Homologated Enel DY541/1, UR P001
- Available execution in accordance with CEI 0-16
- On request: sealable cover on secondary terminals

MOD: ESR24L Serie: CGS 20.68 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
WITH HORIZONTAL BUILT-IN FUSEHOLDER
MOD: EVR24D
Series: CGS
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Suitable to 24kV 2A fuses
- On request: sealable cover on secondary terminals

MOD: EVR24D Serie: CGS 20.41 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKM24/2
Series: BALTEAU
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V; rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Available execution in accordance with CEI 0-16
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: UKM24/2 Serie: BALTEAU 19.02 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKM24/3
Series: BALTEAU
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Available execution in accordance with CEI 0-16
- On request: sealable cover on secondary terminals

MOD: UKM24/3 Serie: BALTEAU 261.96 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKP24/2
Series: BALTEAU
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 20000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- Different characteristics upon agreement
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: UKP24/2 Serie: BALTEAU 19.12 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKP24/3
Series: BALTEAU
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 20000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: UKP24/3 Serie: BALTEAU 19.93 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
WITH VERTICAL BUILT-IN FUSEHOLDER
MOD: UR2-18F
Series: BALTEAU
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 20000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- ypical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- Different characteristics upon agreement
- Suitable to 24kV 6,3A fuses
- On request: sealable cover on secondary terminals

MOD: UR2-18F Serie: BALTEAU 16.16 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: ESR36D
Series: CGS
- Highest insulation level 36/70/170 Kv
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 800 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: ESR36D Serie: CGS 204.03 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: ESR36L
Series: CGS
- Highest insulation level 36/70/170 Kv
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 800 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: ESR36L Serie: CGS 148.55 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKH36
Series: BALTEAU
- Highest insulation level 36/70/170 Kv
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 30VA/Cl.0,2 - 90VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 350 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: UKH36 Serie: BALTEAU 261.45 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKM36
Series: BALTEAU
- Highest insulation level 36/70/170 kV
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 75VA/Cl.0,2 - 200VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 800 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: UKM36 Serie: BALTEAU 209.36 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
WITH VERTICAL BUILT-IN FUSEHOLDER
MOD: UR3-18F
Series: BALTEAU
- Highest insulation level 36/70/170 Kv
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings; with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h; frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Suitable to 36kV 6,3A fuses
- On request: sealable cover on secondary terminals

MOD: UR3-18F Serie: BALTEAU 286.34 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
WITH VERTICAL BUILT-IN FUSEHOLDER
MOD: UR3-18F/2
Series: BALTEAU
- Highest insulation level 36/70/170 Kv
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 70VA/Cl.0,2 - 180VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 800 VA
- Different characteristics upon agreement
- Suitable to 36kV 6,3A fuses
- On request: sealable cover on secondary terminals

MOD: UR3-18F/2 Serie: BALTEAU 204.23 KB
INDOOR VOLTAGE TRANSFORMER SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: UKM52
Series: BALTEAU
- Highest insulation level 52/95/250 kV
- Rated primary voltage up to 45000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 70VA/Cl.0,2 - 180VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 800 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: UKM52 Serie: BALTEAU 234.02 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VDR12C
Series: DIN
- Highest insulation level 12/28/75 kV
- Rated primary voltage up to 11000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 30VA/Cl.0,2 - 80VA/Cl.0,5
- Maximum thermal burden: 450 VA
- Different characteristics upon agreement
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: VDR12C Serie: DIN 188.16 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VDR24D
Series: DIN
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 23000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- Dimensions in accordance with DIN 42600 Schmale Bauform
- On request: sealable cover on secondary terminals

MOD: VDR24D Serie: DIN 190.11 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VKP24/2
Series: BALTEAU
- Highest insulation level 17,5/38/95 kV
- Rated primary voltage up to 15000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 30VA/Cl.0,2 - 80VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: VKP24/2 Serie: BALTEAU 280.03 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VSR24D
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 23000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: VSR24D Serie: CGS 166.30 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VSR24F
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 22000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: VSR24F Serie: CGS 229.78 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VSR24L
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 22000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- According to CIMEC prescription and CEI- UNEL 21807 specification from 12 up to 24 kV
- On request: sealable cover on secondary terminals

MOD: VSR24L Serie: CGS 203.83 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VKM 24 2 H
Series: BALTEAU
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 23000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Typical performances: 50VA/Cl.0,2 - 130VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: VKM 24 2 H Serie: BALTEAU 314.26 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VKM36
Series: BALTEAU
- Highest insulation level 36/70/170 kV
- Rated primary voltage up to 33000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 75VA/Cl.0,2 - 200VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: VKM36 Serie: BALTEAU 281.03 KB
INDOOR VOLTAGE TRANSFORMER DOUBLE POLES RESIN INSULATED PHASE TO PHASE CONNECTION
MOD: VSR36L
Series: CGS
- Highest insulation level 36/70/170 kV
- Rated primary voltage up to 33000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 75VA/Cl.0,2 - 200VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement
- On request: sealable cover on secondary terminals

MOD: VSR36L Serie: CGS 183.33 KB
OUTDOOR VOLTAGE TRANSFORMER
SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: URE24
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h; frequency 50 or 60 Hz
- Typical performances: 20VA/Cl.0,2 - 50VA/Cl.0,5;
- tertiary 30VA/Cl.3P
- Maximum thermal burden: 400 VA
- Different characteristics upon agreement

MOD: URE24 24kV1p 245.02 KB
OUTDOOR VOLTAGE TRANSFORMER
SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION
MOD: URE36
Series: CGS
- Highest insulation level 36/70/170 kV
- Rated primary voltage up to 33000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement

MOD: URE36 36kV1p 149.63 KB
OUTDOOR VOLTAGE TRANSFORMER DOUBLE POLES INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VRE24
Series: CGS
- Highest insulation level 24/50/125 kV
- Rated primary voltage up to 23000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 20VA/Cl.0,2 - 50VA/Cl.0,5
- Maximum thermal burden: 400 VA
- Different characteristics upon agreement

MOD: VRE24 24kV 2 p 66.34 KB
OUTDOOR VOLTAGE TRANSFORMER DOUBLE POLES INSULATED, FOR PHASE TO PHASE CONNECTION
MOD: VRE36
Series: CGS
- Highest insulation level 36/70/170 kV
- Rated primary voltage up to 33000 V;
- rated secondary voltage 100 V or 110 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Voltage factor 1,2 Un/cont.;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5
- Maximum thermal burden: 600 VA
- Different characteristics upon agreement

MOD: VRE36 36kV 2 p 63.19 KB
VOLTAGE TRANSFORMER WITH METALLIZED EXECUTION
SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH OUTER CONE
MOD: EDR24CE
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 15VA/Cl.0,2 - 40VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 200 VA
- Different characteristics upon agreement
- Primary terminal with external cone, cable plug in EN 50181 type A
- On request: sealable cover on secondary terminals

MOD: EDR24CE 355.11 KB
VOLTAGE TRANSFORMER RESIN INSULATED WITH METALLIZED EXECUTION
SINGLE POLE RESIN INSULATED, FOR PHASE TO EARTH CONNECTION WITH OUTER CONE
MOD: EDR24DE
- Highest insulation level 24/50/125 Kv
- Rated primary voltage up to 23000:V3 V;
- rated secondary voltage 100:V3 V or 110:V3 V
- With one or two secondary windings;
- with one or two ratios obtained by secondary taps
- Rated tertiary voltage (for open delta) 100:3 V or 110:3 V
- Voltage factor 1,9 Un/8h;
- frequency 50 or 60 Hz
- Typical performances: 40VA/Cl.0,2 - 100VA/Cl.0,5;
- tertiary 50VA/Cl.3P
- Maximum thermal burden: 500 VA
- Different characteristics upon agreement
- Primary terminal with external cone, cable plug in EN 50181 type A
- Available execution in accordance with CEI 0-16 2012-12
- On request: sealable cover on secondary terminals

MOD: EDR24DE 311.77 KB